5 Basic Operation
NOTICE
location as the CHGR MODE button on legacy AT10.1 chargers. Its
functionality is equivalent in that it changes charge mode between
EQUALIZE and FLOAT.

5.1.3 Changing Equalize Method

The EQUALIZE METHOD button switches the equalize method
between MANUAL TIMER and AUTOMATIC TIMER. The present
equalize method is displayed at the top right of the HOME screen
'Eqlz Mthd: Man' specifies MANUAL TIMER and 'Eqlz Mthd: Auto'
specifies AUTOMATIC TIMER.
To change the Equalize Method:
EQUALIZE METHOD > select other displayed option
When AUTOMATIC TIMER is selected, ATevo will:
• Automatically switch to EQUALIZE mode when power is restored
after a loss of ac power for greater than twelve (12) seconds.
• Start EQUALIZE TIMER.
• Remain in EQUALIZE mode until either the EQUALIZE TIMER
expires or the charge mode is switched back to float mode
manually.
When MANUAL TIMER is selected, ATevo will only switch to
EQUALIZE MODE when the mode is manually changed.
NOTICE
as EQLZ MTHD button on legacy AT10.1 chargers. Functionality is
equivalent in that when pressed, it changes the equalize method. The
Manual Equalize Method (no timer) available in legacy AT10.1 chargers is
not supported by ATevo.