HindlePower ATevo Series Operating/Service Instructions Manual page 112

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

11 Remote Sense
WIRING
• Connect wire from twisted-pair designated as 'DC(+)' to the
positive terminal (A2-TB1[+]), and connect wire designated as
'DC(-)' to the negative terminal (A2-TB1[-]).
• Observing correct polarity, connect battery end of 'DC(+)' wire
to a positive(+) sense location on the battery. Connect battery
end of 'DC(-)' wire to a negative(-) sense location on the battery.
• Verify all connections and polarity.
• DO NOT energize ATevo until you configure Remote Sense
jumpers per Section 11.4.
• After Remote Sense Jumpers have been correctly configured,
replace the safety shield and re-energize ATevo.
TWISTED PAIR
BATTERY SENSE
WIRES
NOTES
• Maximum current is 150mA.
• Run the twisted-pair cable with the sense leads in a dedicated
conduit.
• Fuse each of the sense wires.
96
DC+
DC-
ATevo
CAUTION - HOT
CB1
CB2
COMM
R3-
R3+
Hig
X4
X1
L2-1
L1-2
L1-1
Y1
Y2
CB2 NEG
CB2 POS
L2-2
C2+
C