7.10.4 Battery & Charging Setting
Route:
SETUP
In the BATTERY & CHARGING SETTING screen shown below, you can set up the
following items. The settings must be carried out by qualified service personnel. Please
contact Delta customer service for assistance.
UPS-1.1
BATTERY & CHARGING SETTING
Battery Low Warning
Float Charge Voltage
Set up the maximum permissible speed for the system output
frequency to catch up the bypass frequency variation.
Set up how many power modules that need to be preserved for
redundancy.
When it is impossible for the inverter to reach synchronous phase
lock with the bypass, the output will be terminated during conversion
process according to this setup time.
Set up the time interval for every power module to be converted
from the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
Set up the time interval for the system to be converted from
the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
Battery & Charging Setting
MEASUREMENT
SETUP
Battery & Charging Setting
PAGE
1
Battery Type
Battery Rating Voltage
168
PbAc
Battery Cut Off Voltage
154
140
V
Equalized Charge Voltage
190
196
V
Description
MAINTENANCE
LOG IN
EVENT LOG
Administrator
PAGE
PAGE
PAGE
2
3
4
Battery Strings
V
1
Capacity
36
V
AH
Charge Current (Max)
8
V
A
7-25
7
LCD Display & Settings