S E TU O F F The power behind competitiveness Delta UPS - Amplon Family N Series, Single Phase 6/ 10 kVA User Manual www.deltapowersolutions.com...
Chapter 1 Important Safety Instructions Chapter 1 : Important Safety Instructions 1.1 Safety Instructions Installation Warnings Before installation and usage, please read this User Manual thoroughly. This helps you to use the product correctly and safely. Install the UPS in a well-ventilated area, away from excess moisture, heat, dust, and humidity well-controlled indoor area that is free of conductive contaminants.
Page 6
It is strictly forbidden to connect the UPS with: 1. any regenerative-type loads. To ensure reliable operation of the UPS and to protect the UPS from overheat- ing, the slits and openings in the UPS must not be blocked or covered. Before usage, you must allow the UPS to adjust to room temperature for at least one hour to avoid moisture condensing inside the UPS.
Page 7
Chapter 1 Important Safety Instructions The risk of electric shock and short-circuit current is possible when the batteries and battery packs are connected to the UPS. Before maintenance, disconnect all batteries and battery packs to cut off the battery power. For battery replacement, only use the same number and type of batteries.
1.2 Standard Compliance EN 62040-1 EN 62040-2 Category C2 1.3 Storage Prior to installation If the UPS needs to be stored prior to installation, it should be placed in a dry area. The allowable storage temperature is between -15°C and +50°C. After usage Press the button for 3 seconds and release it after you hear a beep, make...
Chapter 2 Introduction Chapter 2 : Introduction 2.1 General Overview The N series UPS is a single-phase on-line UPS providing reliable and consistent sine-wave quality power to your electronic equipment. It adopts the latest technol- ogy and the highest quality components providing output power factor up to unity, provides safe, reliable and uninterrupted power to your sensitive electronic equip- Its compact design does not occupy much space and is easy to use.
2.3 Package List For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ) SETUP SETUP The power behind competitiveness Delta UPS - Amplon Family N Series, Single Phase 6/ 10 kVA User Manual www.deltapowersolutions.com Item Q’ty 1 PC Parallel Cable...
Page 11
Chapter 2 Introduction For models UPS602N2004N0B0 (6 kVA ) & UPS103N2004N0B0 (10 kVA ) SETUP SETUP The power behind competitiveness Delta UPS - Amplon Family N Series, Single Phase 6/ 10 kVA User Manual www.deltapowersolutions.com Item Q’ty 1 PC Parallel Cable...
Page 12
For models UPS602N2004N0BA (6 kVA ) & UPS103N2004N0BA (10 kVA ) SETUP SETUP The power behind competitiveness Delta UPS - Amplon Family N Series, Single Phase 6/ 10 kVA User Manual www.deltapowersolutions.com Item Q’ty 1 PC Parallel Cable 1 PC...
Chapter 3 Operation Panel Chapter 3 : Operation Panel 3.1 LED Indicators RUN TIME SET IN OUT BATT LOAD TEST 3.3 LCD Display (including 3.4 7-Segment Display & 3.5 16-Segment Display) °C 3.2 Multi-function Buttons SETUP 3.1 LED Indicators Description Indicates the output status.
3.2 Multi-function Buttons Multi- function Description Button The button has two functions. Please refer to the following for detailed information. 1. Buzzer On/ Off: When the buzzer is on, press the button for 0.1 second to turn off the buzzer. When the buzzer is off, press the button for 0.1 second to turn on the buzzer.
Page 15
Operation Panel Multi- function Description Button NOTE : For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ) & UPS602N2004N0BA (6kVA) & UPS103N2004N0BA (10kVA): For automatic regular battery test, you must install the UPSentry 2012 software (please download from http:// www.deltapowersolutions.com/en-in/mcis/software-...
Page 16
Multi- function Description Button 2. Scrolling Down/ Decreasing Number: Press the button for 0.1 second to go to the next display or to decrease number. 3. Fault Clear: When the UPS has a fault condition, press and hold the button for 3 seconds, release it after you hear one beep and the UPS will clear the fault condition and return to standby mode.
Chapter 3 Operation Panel 3.3 LCD Display RUN TIME SET IN OUT BATT LOAD TEST °C Icon Naming Description Indicates the input source status. Icon 1. ON: The AC input is within the acceptable bypass range. 2. Flashing: The AC input is out of the accep- table bypass range but is able to let the unit operate in on-line mode.
Page 18
Icon Naming Description Inverter Indicates the inverter status. Icon 1. ON: The inverter is running. 2. OFF: The inverter is not running. Standby Illuminates when the UPS is operating in stand- Mode by mode. Graph Online Illuminates when the UPS is operating in on- Mode line mode.
Chapter 3 Operation Panel Icon Naming Description 2. Only when the parallel icon illumi- nates can you perform turn on proce- dures for parallel units. Load 1. ON: Level loads * 2. Flashing: Overload. Graph Battery 1. ON: Level 2. Flashing: Low battery. Graph NOTE : means that:...
Page 20
Display Meaning Category 7-segment Number display Setup mode. Please refer to Input Status Output BATT Battery status LOAD Load status The combination of the three TEST Test categories (left-hand side) presents relevant information Ampere hour such as input voltage, output voltage, output frequency, Current load capacity etc.
Chapter 3 Operation Panel 3.5 16-Segment Display RUN TIME SET IN OUT BATT LOAD TEST °C Display Meaning Category Number/ Error code (For 16-segment error code information, display please refer to The combination of the three cat- egories (left-hand Input side) presents relevant infor- Battery...
Display Meaning Description The warning icon will illuminate when any of the following situations occurs. 1. When the fault LED illuminates. Warning 2. When an abnormality such as overload or battery missing is detected. 3. When the 16-segment display shows an error code.
Chapter 3 Operation Panel In battery mode, here displays In any mode (except battery mode), the remaining battery time. here displays the input voltage. RUN TIME RUN TIME SET IN BATT LOAD TEST SET IN BATT LOAD TEST °C °C 3.7 LCD Display Flow Chart screen.
Page 24
Bypass Mode RUN TIME RUN TIME Input Internal OUT BATT LOAD TEST SET IN OUT BATT LOAD TEST Voltage Temperature °C °C T>0.1S T>0.1S RUN TIME RUN TIME Battery Input OUT BATT LOAD TEST SET IN OUT BATT LOAD TEST Remaining Frequency Time...
Rear Panel Chapter 4 : Rear Panel For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ) EX TE R N A L B A TT . C O N N E C TO R EX TE R N A L B A TT . C O N N E C TO R 240Vdc.48A...
Page 26
Item Functions Input Breaker It is the input power’s protective device and is for safety protection. RS-232 Port Connects to your computer. You can monitor the UPS’s status via your computer by installing the UPSentry 2012 software (please download from http://www.deltapowersolutions.com/en/mcis/ software-center.php).
Page 27
Chapter 4 Rear Panel For models UPS602N2004N0B0 (6 kVA ) & UPS103N2004N0B0 (10 kVA ) MINI SLOT MINI SLOT EXTERNAL BATT. CONNECTOR 240Vdc.48A EXTERNAL BATT. CONNECTOR 240Vdc.48A PARALLEL PARALLEL RS-232 REPO REPO PARALLEL PARALLEL RS-232 REPO REPO AC IN P U T UPS O U T PU T AC IN P U T UPS O U T PU T...
Page 28
Item Functions RS-232 Port Connects to your computer. You can monitor the UPS’s status via your computer by installing the UPSentry 2012 software (please download from http://www.deltapowersolutions.com/en/mcis/ software-center.php). NOTE : Do not use the USB port and the RS-232 port at the same time. If you connect the USB cable to the USB port, the RS-232 port will disable right away.
Page 29
Chapter 4 Rear Panel For models UPS602N2004N0BA (6 kVA ) & UPS103N2004N0BA (10 kVA ) SMART SLOT SMART SLOT EXTERNAL BATT. CONNECTOR 192Vdc.58A EXTERNAL BATT. CONNECTOR 192Vdc.58A PARALLEL PARALLEL RS-232 REPO REPO PARALLEL PARALLEL RS-232 REPO REPO AC IN P U T UPS O U T PU T AC IN P U T UPS O U T PU T...
Page 30
Item Functions RS-232 Port Connects to your computer. You can monitor the UPS’s status via your computer by installing the UPSentry 2012 software (please download from http://www.deltapowersolutions.com/en/mcis/ software-center.php). NOTE : Do not use the USB port and the RS-232 port at the same time. If you connect the USB cable to the USB port, the RS-232 port will disable right away.
Chapter 5 Wiring Chapter 5 : Wiring 5.1 Pre-wiring Warnings Before wiring or making any electrical connection, make sure that the UPS is in shutdown status, and the power supplied to the input and output of the UPS is completely cut off to avoid accidents. When connecting the UPS to the mains and the loads, you must install the pro- tective devices.
5.2 Input/ Output Wiring NOTE : 1. The UPS doesn’t have any built-in backfeed protection device. Please install a backfeed protection device in front of the input power. The suggested backfeed protection device rating is as follows: Suggested Backfeed Protection Device Rating 6kVA 240VAC/ 40A 10kVA...
Page 33
Chapter 5 Wiring (A) Connect the provided four CU terminals (type B) to the input cables (L & N) and output cables (L & N), and then connect the four CU terminals (type B) to the AC input terminals and UPS output terminals. (B) Connect the provided two CU terminals (type A) to the input grounding cable and output grounding cable, and then connect the two CU terminals (type A) to the input grounding terminal...
2. The breaker must be a 2-pole non-fuse DC breaker with characteristics of 1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breaking capacity. For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ): Remove the two screws from the external battery connector’s panel shown below.
Page 35
Chapter 5 Wiring Use the provided battery cable holder’s screw (total: 2; the other is the spare part) to install the battery cable holder (provided) on the battery cable Battery Cable Holder’s Screw Battery Cable Battery Cable Holder Insert the battery cable into the external battery connector and use the two screws that were removed from the external battery connector’s .
Page 36
For models UPS602N2004N0B0 (6 kVA ) & UPS103N2004N0B0 (10 kVA ) & UPS602N2004N0BA (6kVA ) & UPS103N2004N0BA (10kVA ): NOTE : For models UPS602N2004N0B0 (6 kVA) & UPS103N2004N0B0 (10 kVA) & UPS602N2004N0BA (6kVA) & UPS103N2004N0BA (10kVA), their external battery pack wiring methods are the same. Below, we only use model UPS103N2004N0B0 (10 kVA) as an example for illustration.
Page 37
Chapter 5 Wiring Battery Terminals (+, -, ) CU Terminal (Type C) x 3 S L O M IN I c .4 8 A R E P R E P 4 0 V d O R 2 E C T R S -2 O N N T T .
Chapter 6 : Operation Modes NOTE : 1. Please refer to to learn how to operate the operation panel and understand the display meaning. 2. Each of the display diagrams shown in this chapter is for reference only. Actual display depends on the operation of the UPS. 6.1 Standby Mode NOTE : the utility AC power, the bypass will supply power to the output directly and...
NOTE : For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ) & UPS602N2004N0BA (6kVA) & UPS103N2004N0BA (10kVA): You can install the UPSentry 2012 software (please download from http://www.deltapowersolutions.com/en-in/mcis/software-center.php) or...
Page 40
3. Frequency converter setup 4. ECO mode setup 5. Overload alarm setup 6. Buzzer setup 7. Charge current setup 8. Battery capacity setup 9. Battery string setup 10. Parallel ID setup For setup procedures, please refer to the following: Simultaneously press the two buttons for 3 seconds to enter into the SETUP setup mode.
Page 41
Chapter 6 Operation Modes Setup Mode Flow Chart Original Display Setup Procedures Illustration Inverter SETUP Voltage Setup T > 3 seconds Inverter T > 0.1 s Frequency Setup T > 0.1 s Frequency Converter Setup T= 0.1 T= 0.1 T > 0.1 s ECO Mode T >...
Page 42
For some settings, they can’t be set in certain operation modes. Please refer to the table below for relevant information. Standby On-line Bypass Battery Setup Item Mode Mode Mode Mode Mode Inverter Voltage Setup Inverter Frequency Setup Frequency Converter Setup ECO Mode Setup Overload Alarm Setup Buzzer Setup...
Chapter 7 Turn-on & Turn-off Procedures Chapter 7 : Turn-on & Turn-off Procedures NOTE : A loss of battery charge capacity may occur during shipping and storage. Before 1 use of the UPS, please (1) check the battery capacity and battery charge setup, and (2) fully charge the batteries until the Battery Level Bar Graph shown on the UPS’s LCD is fully on.
B. Cold Start Please check the ‘+’ and ‘-’ poles and ensure that battery wring is correct. Press and hold the button for 3 seconds and release it after you hear one beep. The UPS starts self-inspection. When the LCD shows , it means that the UPS is running in battery mode.
Chapter 8 Alarm Chapter 8 : Alarm When the external battery pack connected to the UPS has the following problems, the UPS system will sound an alarm. Please see the table below. Condition Alarm Battery Mode Sounds once every 2 seconds. Low Battery Sounds once every 0.5 second.
Chapter 9 : Optional Accessories There are several optional accessories available for this N series UPS. Please refer to the table below for the optional accessories and their descriptions. For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ) Item Function...
Page 47
Chapter 9 Optional Accessories Item Function Monitors and controls the status of the Mini SNMP Card UPS via a network system. Mini Relay I/O Card Increases the quantity of dry contacts. Lets the UPS have USB communication Mini USB Card function.
1. When a problem occur, please check if the following situation exists before contacting Delta service personnel: Is the main input voltage present? 2. Please have the following information ready if you would like to contact the Delta service personnel: Unit information including model, serial number, etc.
Page 49
Chapter 10 Troubleshooting Error Meaning Possible Cause Solution Code E2103 BUS start The UPS has internal Contact service abnormal in abnormalities. personnel. battery mode E2302 +BUS voltage 1. Output connects with 1. Remove any too high regenerative loads. inductive or capacitive loads that 2.
Page 50
Error Meaning Possible Cause Solution Code E6101 Damaged The batteries are Contact service batteries damaged or battery personnel. lifetime is due. E6801 Battery missing 1. The battery cables 1. Check if the battery are not connected or connected or not. 2.
Chapter 11 Maintenance Chapter 11 : Maintenance 11.1 UPS UPS Cleaning Regularly clean the UPS, especially the slits and openings, to ensure that the to clean the slits and openings to prevent any object from blocking or covering these areas. UPS Regular Inspection Regularly check the UPS every half year and inspect: 1.
11.3 Fans Higher temperatures shorten fan life. When the UPS is running, please check if each fan works normally and make sure if the ventilation air can move freely around and through the UPS. If not, contact service personnel. NOTE : Please ask your local dealer or customer service for more maintenance information.
Page 53
Appendix 1 Model N-6K N-10K Power Rating 6kVA/6kW 10kVA/10kW Waveform Pure Sine Wave Nominal Voltage 200/208/220/230/240 Vac 176Vac ~ 280Vac Voltage Range 2. 220/230/240 Vac: 195Vac ~ 280 Vac Input Frequency 40Hz ~ 70Hz Power Factor > 0.99 (full load) iTHD Power Factor Nominal Voltage...
Page 54
Model N-6K N-10K 192 ~ 264Vdc (adjustable) 0B0 & 035 Models: Battery Voltage 240Vdc (default) 192Vdc (default) 0BA Model: Battery 192Vdc (default) Battery Type Sealed VRLA battery Charge Current 1.5 ~ 8A (selectable) 035 & 0BA REPO x 1, RS-232 Port x 1, USB Port x 1, Models Parallel Port x 2, Smart Slot x 1 Communication...
Appendix 2 Warranty Appendix 2 : Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation.