7.10.4 Battery & Charging Setting
Path:
SETUP
In the BATTERY & CHARGING SETTING screen*
Please contact Delta customer service for assistance.
BATTERY & CHARGING SETTING
Whether it is 'Equalized Charge Voltage' or 'Restore Voltage' shown in this
column, it is determined by 'Battery Type'. Please refer to the table shown in
Page 7-46 for more information.
Modulon DPH Series
Set up the time interval for every power module to be converted
from the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
Set up the time interval for the system to be converted from
the battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
NOTE:
1
*
means that the Administrator password is needed. For password information,
please refer to 7.5 Password Entry.
UPS-1.1
MEASUREMENT
SETUP
Battery & Charging Setting
Battery Type
Battery Rating Voltage
PbAc
Battery Low Warning
Battery Cut Off Voltage
220
V
Float Charge Voltage
Equalized Charge Voltage
272
V
Description
1
MAINTENANCE
LOG IN
Administrator
PAGE
PAGE
PAGE
PAGE
1
2
3
4
Battery Strings
240
V
1
Capacity
450
210
V
Charge Current (Max)
280
45
V
7-44
10:15
Sep 25,2018
EVENT LOG
Bypass
Submit
A
A