Switch Off The Input/ Bypass Breaker (Q1) And Output Breaker (Q3). After That, The Ups Will Run In Standby Mode - Delta Modulon DPH Series User Manual

Three phase 15-60 kva 208vac
Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

5
Click
UPS-1.1
MEASUREMENT
MODE SETTING
On-Line
6
Switch OFF the Input/ Bypass Breaker (Q1) and Output Breaker (Q3). After that, the
UPS will run in standby mode.
7
8
About 3 minutes later, the UPS will shut down and the LCD and the tri-color LED
9
Switch OFF every external battery cabinet's breaker.
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
simultaneously executed and performed to all of the parallel UPSs.
parallel ones, please contact service personnel.