7.6.4
Battery & Charging Setting
Path:
→ Battery & Charging Setting
Item
Battery Type
Battery Rating Voltage Set up the battery rating voltage.
Battery Strings
Battery Low Warning
Battery Cut Off
Voltage
Capacity
Float Charge Voltage
Equalized Charge
Voltage
Modulon DPH Series
Set up the battery type as VRLA/ LiB (Dry Contact)*
2
(Integration)*
.
NOTE:
1
1. *
If you use non-Delta lithium-ion batteries,
please set up the battery type as 'LiB (Dry
Contact)'. Please refer to 4.1.6 Input Dry
Contacts and 7.6.6 Dry Contact Setting. For
more information about configurations of the
lithium-ion batteries, please contact Delta
customer service.
2
2. *
If you use the Delta lithium-ion batteries, please
set up the battery type as 'LiB (Integration)'. The
item 'LiB (Integration)' will only appear on the
LCD if you use the Delta lithium-ion batteries with
the optional multifunctional communication card
(MFC) being installed in the SMART slot. Please
contact Delta customer service if you need more
information.
Set up how many battery strings that are used on site.
Set up the battery low warning voltage.
Set up the battery low voltage. In Battery mode, when the
battery low voltage is reached, the battery power will be cut
off, and inverter of the UPS will shut down. The loads will then
be transferred to bypass if the bypass is available; otherwise,
the UPS will shut down.
Set up the battery capacity.
Set up the float charge voltage.
Set up the equalized charge voltage.
NOTE:
The item will only show up if the Battery Type is set
as ' VRLA'.
122
Description
1
/ LiB