7.10.4 Battery & Charging Setting
Path:
SETUP
In the BATTERY & CHARGING SETTING screen (shown in the figure below), the user
can set up the following items. These settings must be carried out by qualified service
personnel. Please contact Delta customer service for assistance.
BATTERY & CHARGING SETTING
BATTERY & CHARGING SETTING
Ultron HPH Series
UPS-1.1
MEASUREMENT
SETUP
Battery & Charging Setting
Battery Type
Battery Rating Voltage
PbAc
Battery Low Warning
Battery Cut Off Voltage
220
V
Float Charge Voltage
Equalized Charge Voltage
272
V
UPS-1.1
MEASUREMENT
SETUP
Battery & Charging Setting
Auto Equalized Charge
Disable
MAINTENANCE
LOG IN
Administrator
PAGE
PAGE
PAGE
PAGE
1
2
3
4
Battery Strings
240
V
1
Capacity
210
450
V
Charge Current (Max)
280
45
V
MAINTENANCE
LOG IN
Administrator
PAGE
PAGE
PAGE
PAGE
1
2
3
4
Auto Equalized Charge Interval
1 Month
7-26
09:30
May 10,2018
EVENT LOG
Bypass
Submit
A
A
09:30
May 10,2018
EVENT LOG
Bypass
Equalized Charge Time
480
min