4
SETTINGS AND PROCEDURE TO OPERATION

4.6 Self-diagnostics Test

This section explains the self-diagnostics test designed for checking the MES interface
module communication function and hardware.

4.6.1 Self-loopback test

Execute the self-loopback test for a hardware check including the communication function
of the MES interface module (10BASE-T/100BASE-TX interface).
(1) MES interface module operation mode setting
1
2
(2) Self-loopback test execution
1
2
3
4
(3) Confirmation of the self-loopback test result
1
OFF
ON
2
3
In [Switch setting for I/O and intelligent function module] of GX Developer, set
"Mode setting" to "Self-loopback test". (Switch 1: 0002h)
Match the other intelligent function module switch settings to the setting contents
used.
If a cable has been connected to the 10BASE-T/100BASE-TX interface,
disconnect it.
Set the programmable controller CPU to STOP status.
Reset the programmable controller CPU.
After the programmable controller CPU is reset, the following self-loopback test is
*1
executed automatically.
1) Self-loopback check
This test checks whether data can be sent to/received from in the MES
interface module.
*1
For a MELSEC iQ-R series system with an MES interface module, do not use the system monitor
of GX Works3 during the self-loopback test. It is not necessary to use the system monitor of GX
Works3 during the self-loopback test.
Check the ERR. LED status to see the self-loopback test result.
Table 4.7 Self-loopback test result
ERR. LED status
When the test is completed normally, set the "Mode setting" to "Online" with
[Switch setting for I/O and intelligent function module] of GX Developer and reset
the programmable controller CPU. (Switch 1: 0000h)
When the test has failed, conduct the self-loopback test again.
If an error occurs again, a possible cause is the hardware failure of the MES
interface module. Please consult your local Mitsubishi representative.
During the test, the ERR. LED flashes.
Self-loopback test result
Completed
Failed
4.6 Self-diagnostics Test
4.6.1 Self-loopback test
1
2
3
4
5
6
7
8