TROUBLESHOOTING
Error code
0495h
0496h
04D0h
0501h
0502h
0604h
0607h
060Ah
0610h
0617h
0618h
0619h
061Ah
0626h
0627h
0628h
0629h
062Ah
062Ch
062Dh
Table 10.3 Error codes for the MES interface module
Error name
Failed to check the CompactFlash
CF card check error
card.
The access to the CompactFlash card
timed out while waiting for a response
CF card response error
from the card. (CompactFlash card
failure)
The battery voltage dropped, or the
Battery error
battery connector was disconnected.
An error was detected from the CPU
CPU fault detected
of the module mounting station.
APS of the request packet does not
match the one of the response packet.
APS mismatch
The Start I/O specified in [Access
target CPU settings] is incorrect.
Failed to read out the setting file. (The
Setting file error
setting file is corrupted.)
The device name specified in the
Component device error
"component setting" is incorrect.
Or, an invalid device was specified.
Information on the network
Access target CPU setting
communication route set in [Access
error
target CPU settings] is corrupted.
Unable to handle the processing due
Module stop error
to a module stop error.
Because the load applied to the
Setting update time-out
module is high, setting update timed
error
out.
The device name specified in [Device
Device name error
tag settings] is erroneous or invalid.
A value which cannot be properly
BCD type conversion
expressed in BCD type was stored in
error
the device.
Invalid multiple CPU settings was
Multiple CPU setting error
configured in [Access target CPU
settings].
The network No, head I/O, or station
Network communication
No. of the network route, which was
route error
specified in [Access target CPU
settings], is out of range.
Tag sampling interval
The sampling interval set in [Device
setting error
tag settings] is invalid.
Failed to read out the setting file. (The
Setting file error
setting file is corrupted.)
The access target CPU specified in
No CPU specification
the "component setting" does not
error
exist, or its setting was deleted.
Description
10.2 Error Code List
10.2.1 Error codes for the MES interface module
(From the previous page)
Action
• Check the CompactFlash card for
any error. (Perform check disk on
the personal computer.)
• Replace the CompactFlash card
with another.
• Replace the battery.
• Check the battery connection.
• Check the CPU status of module
mounting station.
• Retry the transmission.
• Correct [Access target CPU
settings].
• Retry writing the setting with MES
Interface Function Configuration
Tool.
• Correct the device specified in the
"component setting".
• Initialize the module, and then
configure the [Access target CPU
settings] again.
• Remove the cause of the module
stop error, and reset the
programmable controller CPU.
• Re-execute the setting update.
• Reset the programmable controller
CPU.
• Refer to the accessible device list,
and reenter a correct device name.
• Check the settings in [Device tag
settings].
• Check if the value stored in the
device can be properly expressed in
BCD type.
• Correct [Access target CPU
settings].
• Correct [Device tag settings].
• Retry writing the setting with MES
Interface Function Configuration
Tool.
• Specify an existing CPU as the
access target.
(To the next page)