10
TROUBLESHOOTING
(2) Access log of DB Connection Service
Error code
*1
0x20100001
*1
0x20100002
0x20100010
*1
0x20100011
*1
0x20100012
0x20100013
*1
0x20200001
*1
0x20200002
0x20200003
0x20300001
Table 10.7 Access log output error list of DB Connection Service
Error description and cause
(Service Not Start.)
Failed to start the service due to insufficient
memory.
(Service Not Start.)
Failed to start the service due to insufficient
resources.
System error
(Service Not Start.)
Failed to start the service due to failure of the
server port initialization.
(Service Not Start.)
Another application has opened the server port.
System error
(Not Initialize a service for each client: [IP address])
Failed to initialize a service for each client due to
insufficient memory.
(Deny network connection request from [IP
address])
Rejected the connection request from the non-
permitted IP address.
System error
(SID [Session ID]: Request Receive Error: [IP
address])
Failed to receive data due to insufficient memory.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Please consult your local Mitsubishi
representative.
• If firewall software has been installed, set the
specified server port operational.
• Terminate the application that has opened the
server port.
• Set another server port No. with DB Connection
Service Setting Tool.
• Please consult your local Mitsubishi
representative.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Using DB Connection Service Setting Tool, add
the IP address to those with connection
permission.
• Please consult your local Mitsubishi
representative.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
10.2 Error Code List
10.2.2 Error codes of DB Connection Service
Corrective action
(To the next page)