7
MES INTERFACE FUNCTION CONFIGURATION TOOL
Tag component
7
- 96
7.11 Job Setting - Actions
7.11.2 Setting items in Communication action (Select/Update/Insert/MultiSelect/Delete)
(a) When [Select] is selected for [Action type]
[Select] substitutes a field value of the record, whose conditions are met, for a
substitute value (tag component value/variable).
Set conditions of the record to be selected in [Select/Update/Delete conditions].
(6) Select/Update/Delete conditions in this section
Conditions for sorting the selected records are set in [Select sort settings].
(7) Select sort settings in this section
1) Field name (Up to 32 characters)
Set a field name for the field value to be selected.
For characters that can be used for field names, refer to the following:
Appendix 2.4 Characters available for field names, table names, stored
procedure names,etc.
For browsing the field names in the database, refer to the following:
(8) Browse field name in this section
2) Tag
Select a tag or variable for which a value is substituted.
Note that the following tags are not selectable.
• Tags for which [Prohibit data writing] is enabled
• Tags for which [Array setting] is set.
3) Component
Select or directly enter a component value or a variable of the substitution
target.
Database: DB1, Table name: RecipeData
Work_No
536
Matched
Process1.Work_No
Process1.RECIPE1
536
Figure 7.71 Operation example of [Select]
Figure 7.70 Setting example of [Select]
RECIPE1
RECIPE2
5
32
Selected
Process1.RECIPE2
32
5
RECIPE3
1
Selected
Selected
Process1.RECIPE3
1