Mitsubishi Electric Melsec Q Series User Manual page 357

Programmable contoller mes interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

10
TROUBLESHOOTING
Error code
0B68h
0B80h
0B81h
0B82h
0B83h
0B84h
0B85h
to
0B87h
0B88h
0B89h
0B8Ah
Table 10.3 Error codes for the MES interface module
Error name
The tag component value specified for
Max. number of acquired
the maximum number of acquired
records illegal
records is 0 or less.
System error
An error occurred in the Ethernet
Communication start error
communication, and the
communication failed to start.
System error
Communication
connection error
An Ethernet communication error has
occurred.
Communication
connection timeout
System error
Message transmission
error
An Ethernet communication error has
occurred.
Message transmission
timeout
System error
Description
10.2 Error Code List
10.2.1 Error codes for the MES interface module
(From the previous page)
Action
• Set 1 or more to the tag component
value specified for the maximum
number of acquired records.
• Please consult your local Mitsubishi
representative.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
• Please consult your local Mitsubishi
representative.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
• Check if the server computer has no
problem, referring to the following.
Section 10.1.1 (2) Checking
an error of the server
computer
• Ask your network administrator
about the firewall setting.
Section 5.1 Installation
• Please consult your local Mitsubishi
representative.
• Check the Ethernet connection.
• Check if [Server service settings] is
correct.
• Check if the ODBC setting is
correct.
• Please consult your local Mitsubishi
representative.
(To the next page)