TROUBLESHOOTING
Error code
0081h
0082h
0083h
0084h
0085h
0087h
to
0089h
00D2h
00D4h
00D7h
00D8h
00D9h
00DBh
00E0h
00E1h
00E2h
00E3h
00E4h
00E8h
00E9h
00EAh
00ECh
00F0h
Table 10.3 Error codes for the MES interface module
Error name
Device type error
The specified device type is invalid.
The specified device number is out of
Device No. error
range.
The number of device points is
Device point error
incorrect.
Write size error
The write size is not correct.
Link parameter error
The link parameter is corrupted.
System error
A request that is not permitted during
RUN time disable error
RUN was issued.
System error
The receive data length or the byte
Receive data length error
length exceeded the limit.
The communication protocol is not
Protocol error
correct.
Address error
The address is not correct.
Write error
Writing is not executable.
The specified station number does not
Station No. error
exist.
The access target CPU is not capable
Processing mode error
of processing the request.
Intelligent function module
The specified intelligent (or special)
specification error
function module is faulty.
Other data error
The request data has an error.
A link module on the access route
received a request that cannot be
Link specification error
handled. (The access route is not
supported.)
System error
The access target is disconnected
Link timeout
from the link during the processing.
The receive buffer of the access target
Special module BUSY
is full, or is not ready for reception.
The receive buffer of the access target
Access target BUSY
is full, or is not ready for reception.
An request was made to a link stop
Link error
station.
Description
10.2 Error Code List
10.2.1 Error codes for the MES interface module
(From the previous page)
Action
• Correct the device type entered in
[Device tag settings].
• Correct the device number entered
in [Device tag settings].
• Check the CPU(s) on the access
route.
• Set a correct link parameter for the
programmable controller CPU(s) on
the access route.
• Please consult your local Mitsubishi
representative.
• Check the CPU(s) on the access
route.
• Please consult your local Mitsubishi
representative.
• Check the cables on the access
route.
• Check the CPU(s) on the access
route.
• Check the station number setting in
[Access target CPU settings].
• Check the PLC series in [Access
target CPU settings].
• Correct the "U \G " buffer
memory data in [Device tag
settings].
• Check the CPU(s) on the access
route.
• Check the access route referring to
the accessible range.
• Please consult your local Mitsubishi
representative.
• Reconnect the access target on the
access route.
• Examine the hardware of the
intelligent (or special) function
module.
• Check the access target.
• Restore the link to connect the
station on the access route.
(To the next page)