15. MR-J3W-0303BN6 SERVO AMPLIFIER
15.5.4 Other function parameters (No.PF
No.
Symbol
PF06
*FOP5 Function selection F-5
Electronic dynamic brake selection
0
0
PF12
DBT
Electronic dynamic brake operating time
Set a operating time for the electronic dynamic brake.
Communication with the controller cannot be made during the electronic dynamic
brake operation due to SSCNET communication brake.
When reconnecting servo amplifier to the communication, be sure to perform after
the setting value of the electronic dynamic brake operating time has passed and
after checking that the motor has stopped.
15.5.5 Option setting parameters (No.Po
No.
Symbol
Po04
**OOP
Function selection O-2
2
0
)
POINT
Each parameter name of Other function parameters (No.PF
manufacturer settings in the parameter setting window of MR Configurator and MR
Configurator2. However, you can set parameter No.PF06 and PF12. The other
parameters are for manufacturer. Do not change them.
Name and function
0
Electronic dynamic brake selection
0: Automatic setting
2: Disabled
Set Electronic dynamic brake operating time with
parameter No.PF12 (DBT).
Setting "0" enables the electronic dynamic brake.
)
POINT
Each parameter name of Option setting parameters (No.Po
manufacturer settings in the parameter setting window of MR Configurator and MR
Configurator2. However, you can set parameter No.Po04. The other parameters
are for manufacturer. Do not change them.
Name and function
0
0
HG-AK servo motor main circuit power supply selection
0: 48VDC selection
1: 24VDC selection
Select a voltage to connect to the main circuit power supply
for connecting a HG-AK servo motor.
When using a HG-AK servo motor with 24VDC, set the
parameter to "1
Overvoltage (33.1) will occur if "1
48VDC.
".
" is set and used with
15 - 43
) are displayed as
Each/
Default
Setting
Unit
common
value
range
Each
0000h
Refer to
function
column.
Each
100
ms
) are displayed as
Each/
Default
Setting
Unit
common
value
range
Common 0000h
Refer to
function
column.
Name
and
0 to
10000
Name
and