7.3

Setting RUN-PAUSE Contacts

RUN-PAUSE contacts can be set. RUN-PAUSE contacts are used to perform remote RUN or STOP, or remote PAUSE using
a contact.
[CPU Parameter]  [Operation Related Setting]  [RUN-PAUSE Contact Setting]
Window
Displayed items
Item
Description
RUN
Set the contact that controls RUN for the CPU module.
PAUSE
Set the contact that controls PAUSE for the CPU module.
When setting the PAUSE contact, be sure to also set the RUN contact. (The PAUSE contact cannot be set
alone.)
7.4

Remote RESET

This function externally resets a CPU module in the STOP state (including that stopped due to an error). Even when the RUN/
STOP/RESET switch of a CPU module is set to RUN, the CPU module can be reset in the STOP state.

Enabling remote RESET

Performing remote RESET requires setting for enabling remote reset.
[CPU Parameter]  [Operation Related Setting]  [Remote Reset Setting]
Window
Displayed items
Item
Description
Remote RESET
Set whether or not to enable the remote RESET.

Executing method

Using an engineering tool
Perform remote RESET with the remote operation of the engineering tool. ( GX Works3 Operating Manual)
By an external device using SLMP
Perform remote RESET with the SLMP command. ( SLMP Reference Manual)
Setting range
• R00CPU, R01CPU, and R02CPU: X0 to X1FFF
• Other CPU modules: X0 to X2FFF
• R00CPU, R01CPU, and R02CPU: X0 to X1FFF
• Other CPU modules: X0 to X2FFF
Setting range
• Disable
• Enable
7.3 Setting RUN-PAUSE Contacts
Default
Default
Disable
7 REMOTE OPERATION
143
7