Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 555

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

How to clear errors
Errors in the Safety CPU can be cleared in the same way as for the standard CPU. ( Page 135 How to clear errors)
The following describes how to clear errors of the safety function module.
■Using the engineering tool
Clear errors with the module diagnostics function of GX Works3. ( GX Works3 Operating Manual)
■Using the buffer memory
Clear errors using operations of buffer memory.
1.
Check the standard program and identify the detected continuation error using Un\G0 (Latest self-diagnostic error code).
2.
Eliminate the cause of the detected continuation error.
3.
Set 1 in Un\G50 (Error clear) in the standard program to clear the error.
*1 After the error is cleared, 0 is automatically set in Un\G50 by the system.