■REMTO instruction
When the system switching is performed while the instruction is being executed (M101 = ON), SM1643 (ON only in one scan
after system switching (standby to control)) will turn on for one scan in the new control system and the REMTO instruction will
be executed again on the station number 10 of the network number 1. When the system switching is performed while a write
instruction such as the REMTO instruction is being executed, execution of the instruction may have been suspended before
completion of writing data to the target module. Thus, insert an interlock in the new control system to read the X signals and
buffer memory status of the target module and to determine whether or not to execute the instruction again.
• DEVICES
DEVICES
SM1643
*1
SB47
*1
SW0A0.9
*2
M100
*2
M101
*2
M102
*2
M103
*2
M104
*1 For details on the link special relays (SB) and link special registers (SW), refer to the manuals for the network used.
*2 Change the device number according to the system.
• Program example
(1) Add an interlock circuit for determining whether or not to execute the instruction again (according to the X signals and buffer memory status of the target
module) as required.
Data stored
System switching check flag (standby system to control system)
Baton pass status of own station
Baton pass status of each station
Write request
At instruction execution
ON at instruction re-execution request due to system switching
Completed without an error
Completed with an error
(1)
29 PRECAUTIONS ON PROGRAMMING