No.
Name
SM80
Detailed information 1: Flag
in use
SM112
Detailed information 2: Flag
in use
SM150
Power-off/power supply
voltage drop detection
SM151
Power supply module
failure detection
SM152
Momentary power failure
detection (power supply
module 1)
SM153
Momentary power failure
detection (power supply
module 2)
SM154
Invalid power supply
module
*1 There are restrictions on the firmware version of the supported CPU module. ( Page 1008 Added and Enhanced Functions)
Data stored
Details
Off: Not used
This relay switches to on if the detailed
On: In use
information n exists when SM0 switched to
on.
Off: Power-on/normal
• This relay turns on when one or more of
power supply voltage
the power supply modules whose power
On: Power-off/voltage drop
has been shut off or power supply voltage
detected/power supply
has dropped (not including a momentary
module not mounted
power failure), or one or more of empty
slots for the power supply module are
detected on the redundant power supply
base unit.
• This relay turns on if causes to turn on
any bits of SD150 have been occurred.
• This relay turns off if causes to turn on
any bits of SD150 have been removed.
• In a multiple CPU system, the flags are
stored only to the CPU No.1.
Off: Not detected/power-
• This relay turns on when one or more
off/no power supply
power supply module failures have been
module
detected on the redundant power supply
On: Detected
base unit.
• This relay turns on if causes to turn on
any bits of SD151 have been occurred.
• This relay turns off if causes to turn on
any bits of SD151 have been removed.
• In a multiple CPU system, the flags are
stored only to the CPU No.1.
Off: Not detected
• This relay turns on when a momentary
On: Detected
power failure of the input power supply to
the power supply 1 or 2 is detected one or
more times. After turning on, this relay
remains on even if the power supply
recovers from the momentary power
failure.
• This relay turns off the flags (SM152 and
SM153) of the power supply 1 and 2
when the CPU module starts up.
• When one of the two power supply
modules is powered off, this relay turns off
the corresponding flag to one powered
off.
• In a multiple CPU system, the flags are
stored only to the CPU No.1.
Off: Valid/power-off/no
• This relay turns on when one or more of
power supply module
invalid power supply modules have been
On: Invalid
detected on the redundant power supply
base unit.
• This relay turns on if a factor to turn on
any bits of SD154 have been occurred.
• This relay turns off if all the factors to turn
on any bits of SD154 have been removed.
• In a multiple CPU system, the flags are
stored only to the CPU No.1.
Set by (setting timing) CPU
S (Status change)
S (Status change)
S (Status change)
S (Status change)
S (Status change)
S (Status change)
Appendix 4 List of Special Relay Areas
ALL
ALL
*1
Rn
RnP
RnPSF
*1
Rn
RnP
RnPSF
*1
Rn
RnP
RnPSF
*1
Rn
RnP
RnPSF
A
*1
Rn
RnP
RnPSF
APPX
805