Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 899

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

Address
Name
Un\G1053
Diagnostic information 1
to
Un\G1064
Un\G1068
Diagnostic information 2
to
Un\G1077
*1 Data is stored at END processing where the value is changed.
*2 When the count exceeds 65535, counting is continued from 1 again.
*3 A slave station specified is being disconnected, the information immediately before the disconnection is stored.
Data stored
Details
*3
Diagnostic information 1
When 1 (valid) is stored in b0 to b7 of Un\G1052, the number of
occupied stations, group number, IP address, the accumulated number
of timeouts, and the accumulated number of disconnection detection
are stored. When 0 (invalid) is stored in b0 to b7 of Un\G1052, 0 is
stored.
■Un\G1053: Number of occupied stations
■Un\G1054: Group number
■Un\G1055: IP address (lower)
■Un\G1056: IP address (upper)
Un\G1055
Un\G1056
1 to 4: First octet to fourth octet
When the IP address has not been set in the parameter, 0 is stored.
■Un\G1063: Accumulated number of timeouts
After the END instruction of the scan where the bit 0 of 'Diagnostic
information display request' (Un\G1050) is turned off and on is
executed, the accumulated number of timeouts that occurred in a slave
station specified in 'Diagnostic request information' (Un\G1051) is
stored.
• 0: No timeouts
• 1 to 65535: Number of timeouts (accumulated number)
■Un\G1064: Accumulated number of disconnection detection
After the END instruction of the scan where the bit 0 of 'Diagnostic
information display request' (Un\G1050) is turned off and on is
executed, the accumulated number of disconnections that detected in
a slave station specified in 'Diagnostic request information' (Un\G1051)
is stored.
• 0: No disconnections
• 1 to 65535: Number of disconnection detection (accumulated
number)
*3
Diagnostic information 2
When Diagnostic information 2 is valid (1 is stored in b8 to b15 of
Un\G1052), the manufacturer code, model code, device version,
module information, error code, and detailed module information are
stored. When Diagnostic information 2 is invalid (0 is stored in b8 to
b15 of Un\G1052), 0 is stored.
■Un\G1068: Manufacturer code
■Un\G1070: Model code (lower)
■Un\G1071: Model code (upper)
■Un\G1072: Device version
■Un\G1074: Module information
■Un\G1075: Error code
■Un\G1076: Detailed module information (lower)
■Un\G1077: Detailed module information (upper)
b15 to b8
b7 to b0
3
4
1
2
*2
Set by
(setting
timing)
S (Status
change)
*2
S (Status
change)
APPX
Appendix 8 Buffer Memory
A
897

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents