<Data type information row>
The data type for each column is displayed. This information is output in the following format: (Data type)[(Additional
information)].
Item
Date column
Data collection interval column
Execution step No. column
Execution program number column
Execution program name column
Index column
Data column
Trigger occurrence information
column
Ex.
The size of the data type information row is determined by the following equation when data logging of 128 points of data
(signed 16-bit integer, decimal format) is performed (The following sections in the "Output" window are set to be output: "Date"
(the output format is YYYY/MM/DD hh:mm:ss.sss), "Data sampling interval", "Execution step No.", "Execution program name
or execution program No.", and "Index").
(16 + 50)(date column) + 16(data collection interval column) + 16(execution step No. column) + 22(execution program
number column) + 24(execution program name column) + 10(index column) + (10 + 14)  128(data column) + 264(the
number of tabs) + 4(CR + LF) = 3494 bytes
<Data name row>
The data name for each column is displayed.
Item
Date column
Data collection interval column
Execution step No. column
Execution program number column
Execution program name column
Index column
Data column
Trigger occurrence information column
Ex.
The size of the data name row is determined by the following equation when data logging of 128 data points from D100 to
D227 is performed (The following sections in the "Output" window are set to be output: "Date", "Data sampling interval",
"Execution step No.", "Execution program name or execution program No.", and "Index").
28(date column) + 24(data collection interval column) + 16(execution step No. column) + 22(execution program number
column) + 24(execution program name column) + 10(index column) + (6  128)(data column) + 264(the number of tabs) +
4(CR + LF) = 1138 bytes
APPX
952
Appendix 13 How to Use CPU Module Logging Configuration Tool
"Data type" output content
DATETIME
INTERVAL
STEP NO.
PROGRAM NO.
PROGRAM NAME
INDEX
Bit type: BIT
16-bit integer (unsigned): USHORT
16-bit integer (signed): SHORT
32-bit integer (unsigned): ULONG
32-bit integer (signed): LONG
Single-precision floating point (32-bit): FLOAT
Double-precision floating point (64-bit):
DOUBLE
Character string type: STRING
Numeric string type: RAW
Time: TIME
TRIGGER
Description
TIME (time zone) is output.
INTERVAL[us] is output.
STEP NO. is output.
PROGRAM NO. is output.
PROGRAM NAME is output.
INDEX is output.
The specified data name is output.
Trigger is output.
Size
"Additional information" output
content
16 bytes
Format is output.
[YYYY/MM/DD hh:mm:ss.sss]
16 bytes
No additional information
16 bytes
22 bytes
24 bytes
10 bytes
6 bytes
Bit type: [1;0]
12 bytes
For decimal format: [DEC.0]
10 bytes
10 bytes
For hexadecimal format: [HEX]
8 bytes
10 bytes
For exponent expression: [EXP.
(number of digits of decimal part)]
12 bytes
12 bytes
Character string type, numeric string
type: the specified data length value
6 bytes
(unit: bytes) is output.
8 bytes
No additional information
14 bytes
[(string occurred)] is output (semicolons
(;), double quotation marks (" "), and
commas (,) cannot be used).
Size
6 to 68 bytes
0 byte
10 bytes
14 bytes
10 bytes
14 to 16 bytes
6 to 10 bytes
0 byte
6 to 512 bytes
Size
28 bytes
24 bytes
16 bytes
22 bytes
24 bytes
10 bytes
512 bytes
14 bytes