4.1.9
RUN, STOP, PAUSE operation processing
The A2CCPU operates in one of the following three states:
(a) RUN state
The PC CPU operates the sequence program repeatedly from step
to the END (FEND) instruction.
(b) STOP state
All outputs (Y) are turned off and sequence program operation is
not executed.
(c) PAUSE state
Execution of a sequence program is suspended. The status of all
outputs (Y) before entering the PAUSE state are saved .
The PC CPU's operation processing in each operation state is
described below.