Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 832

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

No.
Name
SM1653
Memory copy start
SM1654
Memory copy being
executed
SM1655
Memory copy
completion
SM1656
Auto memory copy
SM1673
Tracking transfer
completion flag
SM1679
Error reset (the other
system)
SM1680
Error of the other system
monitoring
SM1681
Latest self-diagnostic
error (including
annunciator ON) (the
other system)
SM1682
Latest self-diagnostic
error (not including
annunciator ON) (the
other system)
SM1683
Detailed information 1:
Flag in use (the other
system)
SM1684
Detailed information 2:
Flag in use (the other
system)
APPX
830
Appendix 4 List of Special Relay Areas
Data stored
Details
Off: Not started
On: Start
Off: Not executed
On: Being executed
Off: Not completed
On: Completed
Off: Disabled
This relay turns on when the automatic
On: Enabled
memory copy is set to enable.
Off: Transfer not completed
On: Transfer completed
OffOn:Standby system
error reset requested
OnOff:Standby system
error reset completed
Off: No error
On: Error
Off: No error
On: Error
Off: No error
On: Error
Off: Not used
On: In use
Off: Not used
On: In use
• When this relay is turned from off to on, the
memory copy from the control system to the
standby system starts. Note that the
memory copy does not start as long as the
I/O number of the copy destination (standby
system CPU module: 03D1H) is not stored
when SM1653 is turned from off to on.
• Initial value is off: The memory copy has not
started.
• This relay is on during the memory copy
from the control system to the standby
system.
• This relay turns off when the memory copy
is completed.
• This relay turns on at the completion of the
memory copy from the control system to the
standby system.
• Initial value is off: Memory copy has not
completed.
• This flag is stored a result of the tracking
transfer operated in the preceding END
processing.
• The flag turns on if any of the tracking
transfers in block 1 to 64 has been normally
completed, and turns off if the tracking
transfers failed due to causes such as
tracking communication error.
• This relay is turned from off to on to clear a
continuation error occurred in the standby
system.
• This relay turns from on to off when the
error reset has been completed.
• Initial value is off.
• This relay turns on if an error occurs on
communications with the other system
when an initial processing (including when
the system is determined while waiting for
the other system starts up) or an END
processing is performed. (This relay turns
on when the bit of SD1648 turns on.)
• This relay turns off when an error is cleared.
• This relay turns on if a diagnostic error
occurs in the CPU module in the other
system. (The relay also turns on if an error
is detected by an annunciator.)
• The SM0 status for the CPU module in the
other system is reflected.
• This relay turns on if a self-diagnostic error
occurred in the CPU module in the other
system. (The relay remains off if an error is
detected by an annunciator.)
• The SM1 status for the CPU module in the
other system is reflected.
• This relay turns on when there is detailed
information 1 for an error occurred in the
CPU module in the other system.
• The SM80 status for the CPU module in the
other system is reflected.
• This relay turns on when there is detailed
information 2 for an error occurred in the
CPU module in the other system.
• The SM112 status for the CPU module in
the other system is reflected.
Set by (setting timing)
CPU
U
RnP
S (Status change)
RnP
RnPSF
S (Status change)/U
RnP
RnPSF
S (Initial)
RnP
S (Status change)
RnP
RnPSF
U/S (Status change)
RnP
RnPSF
S (Initial/every END/
RnP
system switching)
RnPSF
S (Every END)
RnP
RnPSF
S (Every END)
RnP
RnPSF
S (Every END)
RnP
RnPSF
S (Every END)
RnP
RnPSF