Error
Error name
code
1165H
UDP/IP send
failed
1166H
TCP/IP send
failed
1167H
Unsend data
send error
1180H
Redundant IP
address error
11A0H
PID operation
error
APPX
706
Appendix 1 Error Codes
Error details and cause
• Data was not sent correctly with
UDP/IP.
• Data was not sent correctly with
TCP/IP.
• Unsent data found, but could not
be sent.
• The same IP address has been
set as the system A IP address,
system B IP address, and/or
control system IP address
• Network addresses of the system
A IP address, system B IP
address, and control system IP
address are different.
 0)
• A value outside the range (T
S
was specified for the sampling
time (T
).
S
Stop/
Action
continue
Continue
• Check the settings for connection with
the external device.
• Check the operation of the external
device or switching hub.
• Since there may be congestion of
packets on the line, send data after a
certain period of time.
• Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
• Check if the connection cable is
disconnected.
• Check that there is no connection
failure with the switching hub.
• Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Continue
• Check the settings for connection with
the external device.
• Check the operation of the external
device or switching hub.
• Since there may be congestion of
packets on the line, send data after a
certain period of time.
• Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
• Check if the connection cable is
disconnected.
• Check that there is no connection
failure with the switching hub.
• Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Continue
• Check the settings for connection with
the external device.
• Check the operation of the external
device or switching hub.
• Since there may be congestion of
packets on the line, send data after a
certain period of time.
• Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
• Check if the connection cable is
disconnected.
• Check that there is no connection
failure with the switching hub.
• Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Continue
• Set different IP addresses for the
system A IP address, system B IP
address, and control system IP
address.
• Set the same network address for the
system A IP address, system B IP
address, and control system IP
address.
Continue
• Check and correct the sampling time
(T
) value.
S
Detailed
Diagnostic
information
timing
Always
Always
Always
Parameter
At power-on,
information
at RESET
Error location
At instruction
information
execution

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents