Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 837

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

No.
Name
Data stored
SD53
AC/DC DOWN
The number of
AC/DC DOWN
detections
SD60
Number of
Number of
module with
module with
blown fuse
blown fuse
SD61
I/O module verify
I/O module verify
error module
error module
number
number
SD62
Annunciator
Annunciator
number
number
SD63
Number of
Number of
annunciators
annunciators
SD64 to
Table of detected
Detected
SD79
annunciator
annunciator
numbers
number
SD80
Detailed
Detailed
information 1
information 1
information
information
category
category code
Details
The value of this register increments by one and stored as a BIN code, each
time input voltage drops to 85% (AC power)/65% (DC power) or less of the
nominal value while the CPU module is carrying out an operation. A counting
cycle from 0 to 65535 to 0 is repeated.
The lowest number of module in which a fuse blew is stored.
The lowest I/O number of the module which has an error detected by the I/O
module verification is stored.
The annunciator number which is detected first is stored.
The number of detected annunciator is stored.
• Numbers of activated annunciators are sequentially registered into SD64
to SD79, each time an annunciator (F) is turned on by the SET F
instruction.
• Number of the annunciator deactivated by the RST F instruction is
removed from register areas SD64 to SD79, and the numbers of
annunciators which were lined up behind the removed one move forward
one by one. When the number of detected annunciators has already
reached 16, the number of a newly detected annunciator is not stored into
SD64 to SD79.
For details on the annunciator, refer to the annunciator (F) ( Page 334
Annunciator (F))
• Detailed information 1 information category code is stored.
b15
b8
b7
b0
b0 to b7: Information category code
b8 to b15: Unused (fixed to 0)
• The following codes are stored into the information category code.
0: N/A
1: program position information
2: drive number and file name
4: Parameter information
5: System configuration information
6: number of times information
7: time information
24: Failure information
27: System switching information
34: Continuous RUN prevention setting in TEST MODE
37: Data type (tracking transfer) information
38: Tracking transfer trigger information
46: CPU module data backup/restoration folder information
50: Safety station system configuration information
Set by
(setting
timing)
S (Error)
S (Error)
S (Error)
S (Instruction
execution)
S (Instruction
execution)
S (Instruction
execution)
S (Error)
Appendix 5 List of Special Register Areas
CPU
ALL
ALL
ALL
ALL
ALL
ALL
ALL
A
APPX
835

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents