Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 736

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

Error
Error name
code
2520H
Invalid interrupt
2521H
2522H
Invalid interrupt
2610H
Inter-module
synchronization
signal error
2611H
2630H
Multiple CPU
synchronization
signal error
2631H
2800H
I/O number or
network number
specification
error
2801H
2802H
I/O number or
network number
specification
error
2803H
I/O number or
network number
specification
error
2804H
2805H
APPX
734
Appendix 1 Error Codes
Error details and cause
• Even though an interrupt was
requested, there is no interrupt
factor.
• An interrupt was requested from
the module with no interrupt
pointer setting.
• An execution interval error of the
synchronization interrupt program
has been detected.
• An inter-module synchronization
error has been detected.
• An inter-module synchronization
error has been detected.
• An execution interval error of the
synchronization interrupt program
has been detected.
• A multiple CPU synchronization
error has been detected.
• A multiple CPU synchronization
error has been detected.
• The specified I/O number is out of
range (other than 0 to FFH, 3E0 to
3E3H).
• The I/O number of the module that
does not exist was specified.
• The I/O number of the module that
does not support the instruction
was specified.
• The dedicated instruction
specified in the program cannot
be executed in the specified
module or mode.
• The I/O number of the module that
cannot be specified in the
instruction was specified.
• The specified network number is
out of range (other than 1 to 239).
• The network number that does not
exist was specified.
Stop/
Action
continue
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, or module (I/O module or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
Stop
• Check and correct the interrupt pointer
setting in the module parameters.
• Take measures so that no interrupt is
requested from the module with no
interrupt pointer setting.
• Check and correct the interrupt setting
in the buffer memory of the intelligent
function module.
• Correct the BASIC program executed
in the QD51.
Stop/
• Take measures to reduce noise.
continue
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
Stop
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
Stop/
• Take measures to reduce noise.
continue
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or base unit. Please consult your local
Stop
Mitsubishi representative.
Stop/
• Check the detailed information (error
continue
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
Stop/
program (step) by clicking the [Error
continue
Jump] button, and correct the program.
Stop/
• Check the detailed information (error
continue
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Check the execution propriety
(including support status and execution
mode) of the dedicated instruction,
referring to the manual for the target
module.
Stop/
• Check the detailed information (error
continue
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Detailed
Diagnostic
information
timing
System
At interrupt
configuration
occurrence
information
System
At interrupt
configuration
occurrence
information
Always
System
At power-on,
configuration
at RESET, at
information
END
instruction
execution
Always
System
At power-on,
configuration
at RESET, at
information
END
instruction
execution
Error location
At instruction
information
execution
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information,
execution
system
configuration
information