2441H
Module major
error
2442H
2443H
2450H
Module major
error
2460H
Another CPU
module major
error
2461H
2462H
2463H
2470H
2480H
Multiple CPU
error
2481H
Multiple CPU
error
APPX
730
Appendix 1 Error Codes
Error details and cause
• An error has been detected in the
I/O module or intelligent function
module when the instruction was
executed.
• An error has been detected in the
I/O module or intelligent function
module during the END
processing.
• An error has been detected in the
I/O module or intelligent function
module.
• A major error has been notified
from the intelligent function
module connected.
• The I/O module or intelligent
function module is not mounted
properly or was removed during
operation.
• An error has been detected in
another CPU module during the
initial processing.
• An error has been detected in
another CPU module when the
instruction was executed.
• An error has been detected in
another CPU module during the
END processing.
• An error has been detected in
another CPU module.
• A major error has been notified
from another CPU module.
• In a multiple CPU system, an error
has been detected in the CPU
module where "Stop" is set in the
operation mode setting parameter.
• Any CPU module other than CPU
No.1 is mounted in the
inapplicable slot.
(An error occurs in the CPU module
mounted in the inapplicable slot.)
• In a multiple CPU system, any
CPU module other than CPU No.1
was disconnected from the base
unit during operation. Or, any CPU
module other than CPU No.1 was
reset.
Stop/
Action
continue
Stop/
• Take measures to reduce noise.
continue
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the error module.
Please consult your local Mitsubishi
Stop/
representative.
continue
Stop
Stop/
• Take measures to reduce noise.
continue
• Check the connection status of the
extension cable.
• Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
module corresponding to the displayed
slot number.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the error module.
Please consult your local Mitsubishi
representative.
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
Stop/
a hardware failure of the host CPU
continue
module or another CPU module where
the error has been detected. Please
consult your local Mitsubishi
representative.
Stop/
continue
Stop
Stop/
continue
Stop
• Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool, identify the error
module, and eliminate the error cause.
• Remove the CPU module from the
inapplicable slot.
Stop
• Check the mounting status and reset
status of the CPU modules other than
CPU No.1.
Detailed
Diagnostic
information
timing
Error location
At instruction
information,
execution
system
configuration
information
System
At module
configuration
access
information
System
Always
configuration
information
System
At power-on,
configuration
at RESET
information
Error location
At instruction
information,
execution
system
configuration
information
System
At END
configuration
instruction
information
execution
System
At power-on,
configuration
at RESET
information
System
Always
configuration
information
System
Always
configuration
information
System
Always
configuration
information