Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 734

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

Error
Error name
code
24C3H
System bus
error
24C4H
System bus
error
24C5H
24C6H
System bus
error
24C8H
System bus
error
APPX
732
Appendix 1 Error Codes
Error details and cause
• An error was detected on the
system bus.
• An error was detected on the
system bus.
• An error was detected on the
system bus.
• An error was detected on the
system bus.
Stop/
Action
continue
Stop
■CPU module
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
base unit, extension cable, or module
(I/O module or intelligent function
module) connected. Please consult
your local Mitsubishi representative.
■Redundant function module
• The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
• Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the base unit,
extension cable, or module (I/O module
or intelligent function module)
connected. Please consult your local
Mitsubishi representative.
■CPU module
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or extension cable. Please consult your
local Mitsubishi representative.
■Redundant function module
• The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
• Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Stop
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the extension
cable, or module (I/O module or
intelligent function module) connected.
Please consult your local Mitsubishi
representative.
Detailed
Diagnostic
information
timing
System
At module
configuration
access
information
System
At module
configuration
access
information
At module
access
At power-on,
at RESET

Hide quick links: