Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual page 131

Melsec iq-r series cpu module application user's manual
Table of Contents

Advertisement

■Applicable errors to the error detection setting
The following table lists errors for which whether or not to detect the errors can be set.
Error name
Power shutoff (either of the redundant power supply modules)
Failure (either of the redundant power supply modules)
Battery error
Module verification error
Fuse blown error
CPU module operation upon error detection setting
Set the CPU module operation upon error detection.
[CPU Parameter]  [RAS Setting]  [CPU Module Operation Setting at Error Detected]
Window
Displayed items
Item
Instruction Execution
I/O No./Network No.
Error
Specification Error
Device/Label/Buffer
Memory Specification
Incorrect
File Name Specification
Incorrect
Operation Error
*2
Memory Card Error
*1
Module Verify Error
*1
Fuse Blown
Synchronous Interrupt Execution Interval Error
(CPU Module)
*1 For the Process CPU and SIL2 Process CPU, setting "Direct change setting" to "Enable" in "Online module change setting" causes a
continuation error regardless of this setting. For the online module change function setting, refer to the following.
 MELSEC iQ-R Online Module Change Manual
*2 This item is not displayed on the R00CPU.
Error code
1010H
1020H
1090H
2400H, 2401H
2420H
Description
Sets the CPU module operation when a specification error of
I/O numbers/Network numbers has been detected.
Sets the CPU module operation when a specification error of
Device/Label/Buffer memory has been detected.
Sets the CPU module operation upon a file name
specification error.
Sets the CPU module operation upon an operation error.
Sets the CPU module operation upon a memory card error.
Sets the CPU module operation upon a module verification
error.
Sets the CPU module operation upon a fuse blown error of
controlled module.
Sets the CPU module operation upon a detection of a
synchronization signal error on the CPU module.
Setting range
Default
• Stop
Stop
• Continue
6 RAS FUNCTIONS
6.2 Self-Diagnostics Function
6