37.8

Switching Safety Operation Mode

This section describes how to switch the safety operation mode.
Safety operation mode transition timing
The following table shows the timing at which safety operation mode switches.
Safety operation mode switching direction
TEST MODE  SAFETY MODE
SAFETY MODE  TEST MODE
Safety operation mode
Factory default
The CPU module is
powered off or being
reset.
Power-on/Reset of the CPU
module
Writing programs and parameters
TEST MODE
to the CPU module
Mode switching (other than RUN)
(TEST MODE → SAFETY MODE)
SAFETY MODE
(wait-for-restart)
Power-off/Reset of the CPU
module
The CPU module is
powered off or being
reset.
Power-on/Reset of the CPU
module
SAFETY MODE
Mode switching
(SAFETY MODE → TEST MODE)
TEST MODE
The SIL2 Process CPU retains the safety operation mode status even when the CPU module is powered off or
is reset.
User operation
(1)
(2)
(3)
Safety operation mode switch timing
When the CPU module is powered off and on or is reset after the safety
operation mode switching operation
At the safety operation mode switching operation
(1) After switching from TEST MODE to SAFETY MODE, the safety operation
mode will be SAFETY MODE (wait-for-restart). (The status will be wait-for-
restart until the CPU module is powered off or is reset.) An error occurs if
the SIL2 Process CPU is switched to the RUN state when in SAFETY
MODE (wait-for-restart).
(2) After switching the safety operation mode (TEST MODE  SAFETY
MODE), the mode will switch to SAFETY MODE when the CPU module is
powered off and on or is reset.
(3) After switching the safety operation mode (SAFETY MODE  TEST
MODE), the mode will switch to TEST MODE.
37.8 Switching Safety Operation Mode
37
37 FUNCTIONS
655