Appendix 1 Error Codes
Error details and cause
• The IRET instruction does not
exist in the executed interrupt
program.
• The STOP instruction has been
executed in an interrupt program.
• The IRET instruction exists before
the FEND instruction in the main
program.
• The IRET instruction or STOP
instruction was executed in the
fixed scan execution type
program.
• The IRET instruction or STOP
instruction has been executed in
an event execution type program.
• Before the FB/FUN program ends,
the call source program ended.
• The secured temporary area size
exceeded its limit.
• Division where the divisor is zero
was performed.
• Data that cannot be converted by
using the data conversion
instruction was input.
• The operation was performed with
the invalid data (-0, denormalized
number, NaN (not a number), or
).
• An overflow has occurred during
the operation.
• A string that is not supported in
the instruction was specified.
• The input data was out of range.
• The operation result is out of the
output range. (The operation
result of the instruction that
concatenate character strings
exceeded the allowable number of
characters.)
• The link direct device, module
access device, or CPU buffer
memory access device is
specified for both (s) and (d) used
in the BMOV instruction.
Stop/
Action
continue
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the program to the CPU module
again. Then, reset the CPU module
and run it again. If the same error code
is displayed again, the possible cause
is a hardware failure of the CPU
module or module (SIL2 function
module or safety function module)
connected. Please consult your local
Mitsubishi representative.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the number
of nesting levels in the function.
Stop/
• Check the detailed information (error
continue
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Detailed
Diagnostic
information
timing
Error location
At instruction
information
execution
Error location
At instruction
information
execution
Error location
At instruction
information
execution
Error location
At instruction
information,
execution
process
control
instruction
processing
information
Error location
information