Accuracy of timers
This sections describes the accuracy of timers.
■Timer (T/ST)
The scan time value measured by the END instruction is added to the current value when the OUT T instruction is executed.
If the timer coil is turned off when the OUT T instruction is executed, the current value is not updated. The maximum
response accuracy of the timer (the time duration from capture of an input (X) to output of it) is "2 scan time + timer time limit
setting".
Ex.
Timer limit setting = 10ms, setting value of T0 = 8 (10ms  8 = 80ms), scan time = 25ms
END
processing
Program
1
2
Measurement at
10ms interval
Count by the END
2
instruction
Current value of T0
ON
External input of X0
OFF
ON
OFF
X0 of the CPU
module
OFF
Coil of T0
OFF
Contact of T0
Scan time
25ms
(1) Accuracy from when the coil of the timer turns on until when the contact of the timer turns on
- (1 scan time + timer limit setting) to (1 scan time)
(2) Timing on when the coil of the timer turns on
(3) Input fetching timing
END
END
END
processing
processing
processing
2
3
1
1
2
1
2
3
2
0+2=2
2+3=5
ON
25ms
25ms
25ms
(1)
(2)
(3)
X0
END
END
processing
processing
3
1
2
1
2
3
3
2
3
5+2=7
7+3=
ON
25ms
25ms
K8
T0
21 DEVICES
21.3 User Device
21
341