Note
Connecting SINAMICS Integrated online
To connect SINAMICS Integrated online:
• You need STEP 7 Professional and SINAMICS Startdrive (V16 or higher).
• The hardware configuration must have been loaded to the SIMATIC Drive Controller.
• A subnet must be configured at the interface to which you are connecting your PC/PC.
• The configured SINAMICS firmware version must match the firmware version of the
device.
For information on how to determine the firmware version of the device without SINAMICS
Startdrive, refer to the section Determining the SINAMICS Integrated version (Page 153).
You can only configure the drive offline with SINAMICS Startdrive without STEP 7
Professional.
9.3

Configuration procedure

Proceed as follows to create a new project in the TIA Portal and add a SIMATIC Drive
Controller:
Creating a project
1. Start TIA Portal.
2. Select the action "Start" > "Create new project" in the portal view.
3. Assign a name for the new project under "Project name".
4. Set the storage location with the "..." button.
5. If required, enter comments in the Comment field.
6. Click the "Create" button to create the project.
You have created the project and are currently in the portal view. To continue with the
configuration, switch to the project view.
Adding a SIMATIC Drive Controller to the project
1. Select "Add new device" in the project tree.
2. In the "Add new device" dialog, select the device version you are using under "Controller" >
"SIMATIC Drive Controller" and the firmware version of the device under "Version".
3. You use the "Open device view" checkbox to specify whether the hardware configuration
view is to be opened once the device has been created. Keep the checkbox selected if you
want to configure the CPU next.
4. Click OK to confirm the new device.
You have added the SIMATIC Drive Controller to the project and can now continue with
configuration, parameter assignment and programming.
SIMATIC Drive Controller
System Manual, 11/2023, A5E46600094-AD
Configuring
9.3 Configuration procedure