MMI-20016855
6 Integrate the meter with the control
system

6.1 Configure the mA Output

The mA Output is used to report the configured process variable. The mA Output parameters control how the
process variable is reported.
Your transmitter has two mA Outputs.
Important
Whenever you change an mA Output parameter, verify all other mA Output parameters before returning the
meter to service. In some situations, the transmitter automatically loads a set of stored values, and these
values may not be appropriate for your application.
6.1.1 Configure mA Output Process Variable
Display
OFF-LINE MAINT → OFF-LINE CONFG → IO → AO 1 → SRC
OFF-LINE MAINT → OFF-LINE CONFG → IO → AO 2 → SRC
ProLink III
Device Tools → Configuration → I/O → Outputs → mA Output
Field Communicator
Configure → Manual Setup → Inputs/Outputs → mA Output 1 → Primary Variable
Configure → Manual Setup → Inputs/Outputs → mA Output 2 → Secondary Variable
Use mA Output Process Variable to select the variable that is reported over the mA Output. This variable is
applied automatically to the Frequency Output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set Volume Flow Type as
desired: Liquid or Gas Standard Volume.
If you plan to configure an output to report a concentration measurement process variable, ensure that
the concentration measurement application is configured so that the desired variable is available.
If you are using the HART variables, be aware that changing the configuration of mA Output Process
Variable will change the configuration of the HART Primary Variable (PV) and/or the HART Secondary
Variable (SV).
Procedure
Set mA Output Process Variable as desired.
Default settings are as follows:
Primary mA Output: Mass Flow Rate
Secondary mA Output: Density
Postrequisites
If you changed the setting of mA Output Process Variable, verify the settings of Lower Range Value (LRV)
and Upper Range Value (URV).
Configuration and Use Manual

Integrate the meter with the control system

June 2019
75