Integrate the meter with the control system
March 2019
Range: Unlimited
Note
You can set URV below LRV. For example, you can set URV to 50 and LRV to 100 . If you do this, the mA
Output will be inversely proportional to the value of mA Output Source.
Tip
For best performance:
Set LRV ≥ LSL (lower sensor limit).
Set URV ≤ USL (upper sensor limit).
Set these values so that the difference between URV and LRV is ≥ Min Span (minimum span).
This ensures that the resolution of the mA output signal is within the range of the bit precision of the D/A
converter.
Note
The transmitter always stores LRV and URV for the current process variable and the previous process variable.
If mA Output Source is set to Mass Flow Rate and you set LRV and URV for this configuration, then you
change mA Output Source to Volume Flow Rate and set LRV and URV, then change mA Output Source back
to Mass Flow Rate, the corresponding LRV and URV are restored automatically. However, if you changed mA
Output Source to Volume Flow Rate, then to Phase Genius Flow Severity, and then back to Mass Flow Rate,
the configured LRV and URV for Mass Flow Rate are no longer available. The sensor's lower limit and upper
limit are used instead.

8.2.3 Configure mA Output Direction

Menu > Configuration > Inputs/Outputs > Channel x > I/O Settings > Direction
Display
Device Tools > Configuration > I/O > Outputs > mA Output x > Direction
ProLink III
Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mAOx Fault Settings > mAOx
Field Communicator
Direction
mA Output Direction controls how conditions of forward flow and reverse flow affect the flow rates reported
by the mA Output.
Actual flow direction interacts with Sensor Flow Direction Arrow to determine the flow direction that the
transmitter uses in processing. See the following table.
Table 8-1: Interaction between actual flow direction and Sensor Flow Direction Arrow
Actual flow direction
Forward (same direction as Flow arrow
on sensor)
Reverse (opposite from Flow arrow on
sensor)
140
Setting of Sensor Flow Direction
Arrow
With Arrow
Against Arrow
With Arrow
Against Arrow
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166
Flow direction sent to outputs and
totalizers
Forward
Reverse
Reverse
Forward