"Constant light controller" application

11.5.1
General parameters — Output is of type
Options:
1 Byte 0 - 100%: For activating dimmers.
1 Byte 0 - 255: For actuators, which are activated with a value of between 0 and 255.
Note
If the type of output is changed, also the options for setting the parameters
change:
In this manual only values for the 1-byte 0 - 100% setting are described.
11.5.2
General parameters — Bottom limit output 1 (%)
Options:
Here the bottom control limit is specified and up to which minimum value a dimmer is
controlled.
11.5.3
General parameters — Upper limit output 1 (%)
Options:
Here the upper control limit is specified and up to which maximum value a dimmer is
controlled.
11.5.4
General parameters — Control starts at (%)
Options:
Here the value is specified at which the control starts and the lighting is switched on.
11.5.5
General parameters — Control speed (mm:ss)
Options:
Here the time is specified which the control requires to get from 0 to the upper limit output
value. Example: If the control speed is on 10:00 and the lighting is switched on with 50%
and the upper limit is 100%, the control requires 5 minutes to get from 50% to 100%. Vice
versa, the control requires 10 minutes to regulate from 100% to 0%.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
1 byte 0 - 100%
1 byte 0 - 255
Bottom limit output 1
Upper limit output 1
Control starts at
Value for switch-off
0 .. 100
0 .. 100
1 .. 50 .. 100
02:30 .. 10:00 .. 20:00
"Constant light controller" application
│96