11.5.34 Extended parameters — Dimming step size darker (1 to 15)
Options:
Here the step size for reducing the dimming value during blind movement is specified.
Note
If the dimming step size is set too high, the dimming steps will be clearly visible
in the lighting.
11.5.35 Extended parameters — Control speed (mm:ss)
Options:
Here the time is specified which the control requires to get from 0 to the upper limit output
value. Example: If the control speed is on 10:00 and the lighting is switched on with 50%
and the upper limit is 100%, the control requires 5 minutes to get from 50% to 100%. Vice
versa, the control requires 10 minutes to regulate from 100% to 0%.
11.5.36 Extended parameters — Actual brightness filter
Options:
The application reacts to brightness fluctuations (e.g. clouds). The more inactive the filter is
set, the slower the lighting will respond to such fluctuations.
11.5.37 Extended parameters — Exiting manual off dimming mode after (hh:mm)
Options:
When the presence detector receives a value via the "relative dimming" (dimmer) object or a
value > 0 via the "value" (dimmer) object, the presence detector will no longer function
automatically. The presence detector is switched back to automatic mode only after the
movement detected last and the expiry of the set time.
11.5.38 Extended parameters — Exiting manual off mode after (hh:mm)
Options:
When the presence detector receives a switch-off value through the "automatic/manual off"
object or a value = 0 through the "value" (dimmer) object, the presence detector is switched
off and will no longer switch on automatically. The presence detector will function again
automatically only after the receipt of value 1 on the automatic/manual off object or after the
movement detected last and the expiry of the set time.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
1 .. 4 .. 15
00:45 .. 02:30 .. 20:00
quick, approx. 15s
normal, approx. 40s
slow, approx. 75s
00:05 .. 01:00 .. 12:00
00:05 .. 01:00 .. 12:00
"Constant light controller" application