11.19.12 Working mode

Number
12
The "Operating mode" object receives, as a 1-byte value, the operating mode that is to be set.
Here value 1 means "Comfort," value 2 "Standby," value 3 "Economy" and value 4 "Frost/heat
protection".
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller can also be defined by objects "Superimposed operating
mode," "Condensate water alarm," "Dew alarm," "Window contact," "Control On/Off," "Presence
detector" and "Operating mode (listed in decreasing order of priority).
Note
Item 2:
If the master/slave mode is the active operating mode, the Operating mode
(slave) object must be connected to this object.
Item 3:
If the master/slave mode is the active operating mode, the operating mode
(master) object must be connected to this object.

11.19.13 Superimposed operating mode

Number
13
The "Superimposed operating mode" object receives the operating mode that is to be set as 1-
byte value. Here value 0 means "Superimposition inactive," value 1 "Comfort," value 2
"Standby," value 3 "Economy" and value 4 "Frost/heat protection".
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller can also be defined by objects "Superimposed operating
mode," "Condensate water alarm," "Dew alarm," "Window contact," "Control On/Off," "Presence
detector" and "Operating mode (listed in decreasing order of priority).
Note
Item 2:
If the master/slave mode is active, the "Superimposed operating mode" object of
the master and the slave must be connected to the group address of the
transmitter.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Name
1. Operating mode
2. Operating mode (master)
3. Operating mode (slave)
Name
1. Superimposed operating mode
2. Superimposed operating mode
(master/slave)
Communication objects — Object RTC
Object function
Input / output
Input / output
Input / output
Object function
Input
Input
Data type
HVAC mode
HVAC mode
HVAC mode
Data type
HVAC mode
HVAC mode
│184