11.8.3
General — Operating mode after reset
Options:
After a reset the device will run in the operating mode after a restart until a new operating mode
is set as the result of device operation or by communication objects, as the case may be. This
operating mode should be defined during the planning phase. An improperly defined operating
mode can result in a loss of comfort or increased energy consumption.
Comfort: If the room temperature is not automatically lowered and the room is therefore
controlled independent of its use.
Standby: If the room is controlled automatically, e.g. by a presence detector, as a function of
its use.
Eco mode: If the room is controlled automatically or manually as a function of it use.
Frost/heat protection: If only the building protection function is necessary in the room after a
reset.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
11.8.4
General — Additional functions
Options:
This parameter enables additional functions and communication objects, e.g. window
contact and presence detector.
11.8.5
General — Send cyclic "In operation" (min)
Options:
The "In operation" communication object serves to inform that the controller still operates.
Value "1" is sent cyclic. This parameter is used to set the cycle for sending. If the cyclic
telegram fails, the function of the device is faulty and the air-conditioning of the room can be
maintained with a forced operation. However, for this the system and/or actuator must have
"Forced operation" function.
Note
This parameter is only available if the "Additional function" parameter is set to
"Yes".
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Comfort
Standby
Eco mode
Cooling with additional stage
Frost/heat protection
No
Yes
Setting option between 5 - 3000 minutes
Application "RTC object"
│120