Extended Parameters - Use Of Status Of Control Object; Extended Parameters - Overwriting Settings During A Download - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.4.28 Extended parameters — Use of status of control object
Options:
No: There is no separate "status of control" object.
Yes: A 1-bit "status of control" communication object (output) is being enabled. This object
sends a 1 telegram when the constant light switch functions automatically. The object sends
a 0 telegram when manual action takes place, e.g. if a manual switch-off has taken place.
11.4.29 Extended parameters — Overwriting settings during a download
Options:
Yes: When the application is reloaded into the detector, the values changed through the bus
are overwritten with the parameterised values in the ETS application.
No: When the application is reloaded into the detector, the values changed through the bus
are not overwritten with the parameterised values in the ETS application.
Values:
Setpoint
Switch-off delay
Determined brightness of the luminous rows/lamps
Brightness correcting factors
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
Yes
No
Constant light switch application
│92