Setpoint Adjustment - Resetting Of The Manual Adjustment For Receipt Of A Basic Setpoint; Setpoint Adjustment - Resetting The Manual Adjustment For Change Of Operating Mode; Setpoint Adjustment - Resetting The Manual Adjustment Via Object; Setpoint Adjustment - Permanent Storage Of On-Site Operation - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.8.89 Setpoint adjustment — Resetting of the manual adjustment for receipt of a basic
setpoint
Options:
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.
11.8.90 Setpoint adjustment — Resetting the manual adjustment for change of operating mode
Options:
If the device switches to a new operating mode, the manual adjustment is deleted and the
parameterised setpoint temperature for the operating mode plus any change by the base
setpoint value object will be applied if this parameter is activated. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature
in the new operating mode. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. If the system switches to Eco with a parameterised temperature of 17°C, the
device regulates the temperature to 18.5°C, since the manual adjustment is added.
11.8.91 Setpoint adjustment — Resetting the manual adjustment via object
Options:
If this parameter is activated, a separate object can be used to delete the manual adjustment at
any time. Example of application: Resetting the manual adjustment on all devices located in a
building using a system clock.
11.8.92 Setpoint adjustment — Permanent storage of on-site operation
Options:
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. If the device is re-programmed, the stored setpoint values will also be deleted.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
No
Yes
No
Yes
No
Yes
Application "RTC object"