11.3.46 Extended parameter settings (monitoring) — Monitoring time window
Options:
The monitoring time window correlates with minimum activity in the monitoring time window.
The telegram is only sent when a movement is detected within the monitoring time window,
e.g. 50% minimum activity.
Example:
Monitoring time window = 30 seconds
Minimum activity in the monitoring time window = 50%
If someone now moves for 15 seconds within the 30 seconds, the value for switch-on is sent to
the bus. Attention: Depending on the strength of the signal, the sensor will post-oscillate more
or less.
11.3.47 Extended parameter settings (monitoring) — Minimum activity in the monitoring time
window
Options:
See the "Monitoring time window" parameter.
11.3.48 Extended parameter settings (monitoring) — Pause time (ss.fff)
Options:
The set pause time is started after the detector has been switched off due to expiry of the
switch-off delay or when a switch-off telegram is received on objects "external push-button"
or "actuator status".
If movement is detected during this time, the detector is not switched on immediately. The
pause time is first extended by 7 seconds. If there is still movement after these 7 seconds,
the detector switches back on.
If no movement is detected during the pause time, the detector is ready for activation again
after the pause time.
This behaviour can, for example, be important when the lamp cools down drastically and is
located within the detection range of the detector. Without a blockage there would be an
unintentional switch-on. The purpose of pause time is to prevent an immediate re-activation.
Example: The person switches the light off manually when leaving the room. Without the
pause time the detected movement would cause a renewed switch-on during exiting.
Note
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
00:00:01 .. 00:00:30 .. 00:10:00 hh:mm:ss
10% .. 50% .. 100%
00.100 .. 01,250 .. 59,999
The "external push-button" object is activated under the "External push-
button" parameter.
The "actuator status" object is activated under the "status display"
parameter.
"Detector" application
│81