Setpoint Settings; Setpoint Settings - Setpoint For Heating Comfort = Setpoint For Cooling Comfort; Setpoint Settings - Hysteresis For Switchover Heating/Cooling (X 0.1°C); Setpoint Settings - Setpoint Temperature For Heating And Cooling Comfort (°C) - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.8.69 Setpoint settings

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device".
11.8.70 Setpoint settings — Setpoint for heating comfort = setpoint for cooling comfort
Options:
This parameter is used to configure the manner in which the setpoint adjustment functions.
Yes: The device has the same setpoint for heating and cooling in the comfort mode. The
system switches to heating mode when the temperature drops below the setpoint minus
hysteresis. It switches to cooling mode when the temperature exceeds the setpoint plus
hysteresis. The hysteresis can be parameterised.
No: The function has two separate setpoints for heating and cooling in the comfort mode.
The device will display the currently active setpoint value. Switching between heating and
cooling occurs via the "Switchover heating/cooling" parameter setting.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
11.8.71 Setpoint settings — Hysteresis for switchover heating/cooling (x 0.1°C)
Options:
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling mode. If
the room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating mode.
Note
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
11.8.72 Setpoint settings — Setpoint temperature for heating and cooling comfort (°C)
Options:
Specifies the comfort temperature for heating and cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
Setting option between 5 - 100
Setting option between 10 - 40
Application "RTC object"