11.6.2
General parameters — Use of slave input
Options:
No: The option of receiving telegrams from a slave is not available.
Yes: A 1-bit "slave" communication object (input) is being enabled. Via this input the master
detector receives the (On) telegrams of the connected slaves or of a push-button.
11.6.3
General parameters — Slave sends
Options:
Cyclic On telegram: The presence detector, which is connected to the master as slave,
sends only on telegrams cyclically.
On/Off telegram: The presence detector, which is connected to the master as slave, sends
only on/off telegrams.
11.6.4
General parameters — Value for switch-on
Options:
Auto: When movement is detected, value 0 (auto) is sent superimposed via the "HVAC"
object on the bus to the "operating mode" object, to reset the RTC into automatic mode.
Comfort: When movement is detected, value 1 (comfort) is sent via the "HVAC" object on
the bus.
Standby: When movement is detected, value 2 (standby) is sent via the "HVAC" object on
the bus.
ECO: When movement is detected, value 3 (ECO) is sent via the "HVAC" object on the bus.
Frost/heat protection: When movement is detected, value 3 (ECO) is sent via the "HVAC"
object on the bus.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Application "HVAC" (Heating, ventilation, air-conditioning)
No
Yes
Cyclic On telegram
On/off telegram
Auto
Comfort
Standby
ECO
Frost/heat protection