11.3.41 Enable — Use of enable detector object
Options:
No: There is no object with which the detector can be blocked or enabled.
Yes: A 1-bit "enable movement" communication object (input) is being enabled. This object
allows the detector to be enabled or blocked. No telegrams are sent by the detector during
blockage.
11.3.42 Enable — Enable with
Options:
On telegram: With the receipt of value 1 on the "enable movement" (input) object, the
detector is enabled and blocked with value 0.
Off telegram: With the receipt of value 0 on the "enable movement" (input) object, the
detector is enabled and blocked with value 1.
11.3.43 Enable — After bus voltage recovery detector is
Options:
Enabled: The device is enabled and functions normally when the bus voltage is interrupted
or the device has been reprogrammed, as well as after a reset.
Blocked: The device is blocked and must be enabled for normal function when the bus
voltage is interrupted or the device has been reprogrammed, as well as after a reset.
11.3.44 Enable — Output sends at enable
Options:
No telegram: No telegram is sent during enable.
Current status: During enable, the detector checks whether a movement has occurred and
the brightness is below the brightness-value threshold. If yes, the single value for switch-on
is sent. Otherwise the single value for switch-off is sent.
Single value for switch-on: During enable the single value which has been parameterised
under the "value for switch-on" parameter is sent.
Single value for switch-off: During enable the single value which has been parameterised
under the "value for switch-off" parameter is sent.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
On telegram
Off telegram
Enabled
Blocked
No telegram
Current status
Single value for switching on
Single value for switching off
"Detector" application
│79