11.3.15 Extended parameter settings — Operating mode
Options:
Automatic = automatic switch-on and switch-off.
In the "Automatic" mode, the detector switches on automatically when detecting a
movement. The switch-off is effected after the set switch-off delay beginning from the most
recent detection.
Automatic switch-off = manual switch-on and automatic switch-off.
In "Automatic switch-off" mode the detector must be switched on manually using the
"External push-button (input)" object. The switch-off is effected automatically under
consideration of the switch-off delay.
Automatic switch-on = automatic switch-on and manual switch-off.
In "Automatic switch-on" mode, the detector switches on automatically when detecting a
movement. The switch-off is effected by the receipt of an Off telegram on the "External
push-button (input)" object. Note: The detector switches off automatically after 6 hours.
Monitoring = automatic switch-on when there is sufficient movement within a specific time
period and automatic switch-off after a fixed switch-off delay of 2 seconds.
In "Monitoring" mode, the detector switches on brightness-dependent if an adjustable
component of movement has been recorded within the time period set. The switch-off
occurs 2 seconds after switch-on and the last detection of movement.
Note
Manual switch-on and switch-off is possible in operating modes "automatic",
"automatic switch-on" and "automatic switch-off" via the "external push-button"
(input). This external push-button is activated under the "External push-button"
parameter. During manual switch-off the detection of movement is suppressed
for the pause time. The purpose of pause time is to prevent an immediate re-
activation.
Example: The person switches the light off manually when leaving the room.
Without the pause time the detected movement would cause a renewed switch-
on during exiting.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017