11.8.113 Fan coil settings — Fan speed levels — Lowest manually adjustable level
Options:
This parameter is used to preselect the lowest fan speed level that can be set by an operation
performed at the device. When level 0 is selected, the heating/cooling system will not be in
operation (fan speed level and valve control 0) as long as the current operating mode and
operation type are maintained. To avoid damage to the building, level 0 is deactivated after 18
hours and the device is returned to automatic mode.
11.8.114 Fan coil settings — Fan speed levels — Level status evaluation
Options:
The controller obtains the current fan speed level for controlling a fan coil actuator either by
calculating it from the table of level values under "Fan coil settings for heating" or "Fan coil
settings for cooling," or by receiving feedback from the fan coil actuator. If the "Yes" option is
selected, the "Fan coil step status" object is activated for receiving the fan speed level from the
fan coil actuator.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Speed level 0
Speed level 1
No
Yes
Application "RTC object"
│156