11.3
"Detector" application
11.3.1
General parameters — Type of output
Options:
–
Master: In master mode On and Off telegrams are sent (to an actuator) dependent on
movement.
–
Slave: In slave mode On telegrams are sent cyclically (to the extension unit input of a
master detector) when movement is detected.
11.3.2
General parameters — Slave input
Options:
–
No: The option of receiving telegrams from a slave is not available.
–
Yes: A 1-bit "slave" communication object (input) is being enabled. Via this input the master
detector receives the (On) telegrams of the connected slaves or of a push-button. The On
telegram from a slave is comparable with a detected movement.
11.3.3
General parameters — Output is of type
Options:
–
1 Bit: Intended for switch actuators.
–
1 Byte 0 - 100%: For activating dimmers.
–
1 Byte 0 - 255: For actuators, which are activated with a value of between 0 and 255.
–
Light scene number 1 - 64: For activating light scenes.
–
RTC operating mode switchover (1 Byte): To directly switch room temperature controllers
into a specific operating mode.
–
Auto
–
Comfort
–
Standby
–
ECO
–
Frost/heat protection
Note
If the type of output is changed, also the options for setting the parameters
change.
In this manual only values for the 1-bit setting are described.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Master
Slave
No
Yes
1 bit
1 byte 0 - 100%
1 byte 0 - 255
Light scene number 1 - 64
RTC operating mode switchover (1 byte)
–
Value for switch-on
–
Value for switch-off
"Detector" application
│65