11.13
Communication objects — Presence detector — Slave
11.13.1 Px: Enable movement
Number
1 | 19 | 37 |
53
The detector can be blocked or enabled via the object. Enabling has priority over all other
objects.
11.13.2 Px: Actuator status
Number
4 | 22 | 40 |
56
Actuators controlled by the detector can send their status to this input (1 bit). Upon the receipt of
an Off telegram on the object the detection of movement is suppressed for the specified pause
time and the switch-off delay is reset.
11.13.3 Px: Detection independent of brightness
Number
5 | 23 | 41 |
57
If a 1 is received on this object, the detector switches at every movement independent of
brightness. However, if a 0 is received, the detector switches on only when the brightness drops
below the programmed brightness-value threshold and during movement.
11.13.4 Px: External brightness
Number
6 | 24 | 42 |
58
The brightness value of an external brightness sensor is sent to this object.
11.13.5 Px: External brightness-value threshold
Number
7 | 25 | 43 |
59
The external brightness-value threshold can be adjusted via this object. If this value is not to be
overwritten during each download, the parameter "Overwrite setting during download" is to be
programmed accordingly.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Communication objects — Presence detector — Slave
Name
Px: Enable movement
Name
Px: Actuator status
Name
Px: Detection independent of
brightness
Name
Px: External brightness
Name
Px: External brightness-value
threshold
Object function
Object function
Object function
Object function
Object function
Data type
1.001 switch
Data type
1.001 switch
Data type
1.001 switch
Data type
9.* 2-byte float value
Data type
9.* 2-byte float value
│166