11.8.41 Basic stage cooling
Note
Only available when the "Extended settings" parameter under "Cooling control"
is set on "Yes".
11.8.42 Basic stage cooling — Status object cooling
Options:
This parameter enables the "Status cooling" communication object.
11.8.43 Basic stage cooling — Mode of the control value
Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
–
Normal: Value 0 means "Valve closed".
–
Inverse: Value 0 means "Valve open".
11.8.44 Basic stage cooling — Hysteresis (x 0.1°C)
Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
Normal
Inverse
Setting option between 3 - 255
Yes
Application "RTC object"